◇MSPFR806 / 812:Intelligent
and Multifunctional Power Factor Regulator has display of Power Factor(PF),
Voltage(V), Current(A), KVAR, Frequency
(HZ), Temperature ( ℃) and one set of programmable
alarm output.
◇There's no need C/ K value
setup and display automatically the phase value and prevent from abnormal
voltage.
◇Releasing the electricity can protect
the magnetic switch and prolong the life of entire set capacitor, saving
costs in the long term.
◇An independent highly sensitive fuse
and electromagnet connector are incorporated in each set of wires inside
of the controller, maintaining a high level of safety over the long
term.
◇The dry-type capacitor has a metallic
membrane of high compression resistance and electric conductivity. It
contains a safety device and electric discharge with automatic restoring
insulation. When electric wires or capacitors are exceptional, the safety
device inside will automatically cut off electric power to prevent them
from secondary damage.
◇To avoid abnormal voltage, you can
add a serial electric resistance device in the capacitor wires in order
to decrease abnormal voltage.
The
percentage (%) of capacitors (KVA) to loadings (KW)
The Power Factor (PF) after
improving
1.00
.99
.98
.97
.96
.95
.94
.93
.92
.91
.90
.875
.85
.825
.80
.5
.525
.5
.575
173
162
152
142
159
148
138
128
153
142
132
122
148
137
127
117
144
133
123
114
140
129
110
110
137
126
116
106
134
122
112
103
130
119
109
99
128
117
106
96
125
114
104
94
118
107
97
87
111
110
90
80
104
93
83
73
93
87
77
67
.6
.625
.65
.675
133
125
117
109
119
111
103
95
113
105
97
89
108
100
92
84
104
96
88
80
101
92
84
76
97
89
81
73
94
85
77
70
91
82
74
66
88
79
71
64
85
77
69
61
78
70
62
54
71
63
55
47
65
56
48
40
58
50
42
34
.7
.725
.75
.775
102
95
88
81
88
81
74
67
81
75
67
61
77
70
63
57
73
66
58
52
69
62
55
49
66
59
52
45
62
55
49
42
59
52
45
39
56
49
43
36
54
46
40
33
46
39
33
26
40
33
26
19
33
26
19
12
27
20
13
6.5
.8
.825
.85
.875
75
69
62
55
61
54
48
41
54
48
42
35
50
44
37
30
46
40
33
26
42
36
29
23
39
32
26
19
35
29
22
16
32
26
19
13
29
23
16
10
27
21
14
7
19
14
7
13
7
6
.9
.91
.92
.93
.94
48
45
43
40
36
34
31
28
25
22
28
25
22
19
16
23
21
18
15
11
19
16
13
10
7
16
13
10
7
3.6
12
9
6
3.3
9
6
3.1
6
2.8
2.8
0.95
0.96
0.97
0.98
0.99
33
29
25
20
14
18
15
11
6
12
9
5
8
4
3.5
The Power
Factor (PF) before improving
For
Example:
The
power factor of one loading (100KW) is 0.7 If you want to adjust the power
factor as 0.98, through the above table, you can find that the value is 81.
Therefore the capacity should be like 100 X 81% = 81KVAR
Minsun Technology Co., Ltd
15, Lane 210, Jeanshin St. Shulin City, Taipei
Hsien, Taiwan R.O.C